Products

Flame Sensor

FLAME SENSOR FS-5000E
DC 12V

FLAMES DO NOT WAIT!
FS-5000E DETECTS "FLAME" BEFORE IT GROWS INTO "FIRE".
IT DETECTS SMALL FLAMES IMMEDIATELY! AN EPOCHAL ULTRAVIOLET RAY
DETECTION FLAME SENSOR THAT CAN BE USED OUTDOORS.

FLAME SENSOR FS-5000E DC 12V

Data Download

  flile type file name Download
Product pictures JPG Pic_FS-5000E.jpg
Product catalogs PDF Cat_FS-5000E.pdf

go to page top

Feature

GENERAL DESCRIPTI0N

Flame sensor FS-5000E immediately detects ultraviolet rays contained in flames and activates an external output.
Weather proof construction of the housing enables application outdoors. lt can be widely used for fire prevention of areas where fire is prohibited.

8 SELECTABLE SENSITIVITY LEVELS

*2 sensitivity settings High & Low
*4 detection timer settings : 1 sec., 6 sec., 15 sec., 30 sec.
Possibility of false alarms can be reduced.
The set up can be selected from the 8 levels according to the environment of installation.
Area masking enables elimination of unnecessary detection areas.

WHITE BODY MATCHES EVERY LOCATION

Aesthetically pleasing white housing blends well with most surroundings. The unique ball lock mechanism allows for adjustment of the detection area after installation.

CONVENIENT FUNCTI0NS

・ Alarm memory function
Memory indication function enables identification of individual sensors in multiple sensor on configuration.
After raising an alarm, the memory indication LED blinks for 3 minutes and then lights for 47 minutes.

・ Day/night time discernment function
By adjusting operation mode control switch, output operation can be controlled according to ambient light level. Selectable for night time only. (5lux - ∞ lux)

・ Output time set up
Time of detection output operation can be adjusted by a switch [off delay selectable approx. 2 sec. - 1 min. or approx. 5 see. - 10 min.]

go to page top

Specification

Product name Flame sensor
MODEL NO. FS-5000E
Detection system Ultraviolet rays detection
(Detected wave length <185 to 260nm>)
Detection area • Distance
33ft. (10m)
Gas Flame of Lighter in front of sensor :
approx. 2.75”(7cm)33ft.(10m)[2.75"(7cm)flame]

100ft. (30m)
Flame of N-heptane on fire plate 15cm×15cm :
approx. 23.62”(60cm) *The flame size is rough.

• Angle
Vertical : approx. 75degrees (upward : 15degrees)
Hrizontal : approx. 100degrees(downward : 60degrees)

• Adjustment range
Vertical : downward 90degrees(horizontal - vertical)
Horizontal : 180degrees
Sensitivity adjustment ・ Sensitivity
H(100%),L(50%)[selectable by switch]

・ Detection timer
1sec., 6sec., 15sec., 30sec.,[selectable by switch]
Power supply 10V to 30VDC (non-polarity)
Power consumption 35mA or less
Alarm output • Dry contact relay Form C(alarm : open/close)
Contact capacity : 30V(AC/DC)0.5A or less(resistance load)

• Operation time : The following are selectable
* Detection time + off delay operation approx.2sec. - 1 min.
* Detection time + off delay operation approx.5sec. - 10 min.

• Output operation : The following are selectable
* Same time as above continuous outoput
* Same time as above flashing output

• Operation mode(day/night time discernment function) : 5lux(night time operation) - ∞lux(day time operation)adjustment volume
Alarm memory LED(yellow) blinking and lights on /or LED disable.
[selectable by switch]
LED • Operation LED(red) : synchronous dry contact relay
• Memory indication LED(yellow) :After blinking for 3 minutes and auto reset after 47 minutes or reset by manual
Wiring Reed wiring
Power supply : 2 / dry contact : 3
Ambient temp. range -4F to + 122F (-20C to +50C)
lnstaLlation Indoor , Outdoor
Weight approx. 19.3oz(550g)
Appearance Sensor part : PC resin(white)
Adjustment, mounting part : AES resin(white)
Accessories * Tapping screw Φ6 × 30(SUS) : 4pcs
* Tapping screw Φ4 × 8(SUS) : 1pc
* Band : 1pc
* Area mask seal : 1pc

* The specifications are subject to change without notice.

go to page top